number |
project name |
unit |
technical parameter |
|
1 |
rated voltage |
kv |
10 |
|
2 |
maximum operating voltage |
kv |
12 |
|
3 |
rated frequency |
hz |
50 |
|
4
|
1min power frequency withstand voltage |
w |
phase to phase and phase to ground 42, isolation fracture 48 |
|
5 |
lightning impulse withstand voltage |
w |
phase to phase and phase to ground 75, isolation fracture 85 |
|
6 |
rated current of main busbar |
a |
630 |
|
7 |
load switch |
rated current |
a |
630 |
8 |
mechanical life |
second |
5000 |
|
9 |
breaking no-load transformer capacity |
kna |
1250 |
|
10 |
rated thermal stability current |
ma |
20(4s) |
|
11 |
rated dynamic stable current |
ka |
50(peak value) |
|
12 |
rated making current |
a |
50(1peak value) |
|
13 |
combination electrical equipment |
maximum rated current of fuse |
a |
100 |
14 |
rated transfer current |
a |
1500(2000) |
|
15 |
rated short-circuit breaking current |
ka |
31.5 |
|
16 |
distribution fuse model |
|
solaj-12(xrnto-10) |
|
17 |
maximum rated capacity of matched transformer |
kva |
1250 |