serialnumbe |
project name |
unit |
data |
||
|
rated voltage |
kv |
3,6,7.2,12 |
||
2 |
rated current |
a |
630~3150 |
||
3 |
rated short-circuit breaking current |
ka |
20,25,31.5 |
||
4 |
rated short-circuit making current (peak) |
ka |
40,50,80,100 |
||
5 |
rated withstand current (peak) |
ka |
40,50,80,100 |
||
6 |
rated short time withstand current |
ka |
20,25,31.5,40 |
||
7 |
rated insulation level |
1min power frequency withstand voltage lightning impulse withstand voltage |
between poles, between pole to ground fractures between poles, between pole to ground fractures |
w |
24,32,42 |
|
28,38,48 |
||||
1min power frequency withstand voltage |
between poles, between pole to ground fractures |
w |
40,60,75 |
||
w |
46,70,85 |
||||
8 |
rated short-circuit duration |
s |
4 |
||
9 |
protection level |
|
ip2x |
||
10 |
structural style |
|
single busbar segmentation and single busbar with bypass |
||
11 |
operation mode |
|
electromagnetic type, spring energy storage type |
||
12 |
overall dimensions (width × deep x high |
mm |
1200x1300×2650(≥2000a) 1100×1200×2650(general formula) |
||
13 |
weight |
kg |
≈1000 |